Téléchargement | - Voir le manuscrit accepté : AC shunt calibrations at NRC (PDF, 844 Kio)
|
---|
Auteur | Rechercher : Filipski, Peter S.1; Rechercher : Boecker, Michael1 |
---|
Affiliation | - Conseil national de recherches du Canada. Institut des étalons nationaux de mesure du CNRC
|
---|
Format | Texte, Article |
---|
Conférence | 2010 NCSL International Workshop and Symposium, July 25-29, 2010, Providence, Rhode Island, USA |
---|
Résumé | NRC offers calibration of ac shunts from milliamperes up to 100 A, in the 10 Hz to 100 kHz frequency band with expanded uncertainties between 10 A/A for currents in the milliampere range to 50 A/A at 100 A and 100 kHz. The paper describes the design of NRC ac standard shunts, as well as NRC experience in calibrations of commercial shunts. The ac-dc difference of some commercial low current shunts is load sensitive at higher frequency ranges. The paper discusses reasons for this sensitivity and suggests mitigating solutions. |
---|
Date de publication | 2010-08-25 |
---|
Dans | |
---|
Langue | anglais |
---|
Publications évaluées par des pairs | Oui |
---|
Numéro NPARC | 18116650 |
---|
Exporter la notice | Exporter en format RIS |
---|
Signaler une correction | Signaler une correction (s'ouvre dans un nouvel onglet) |
---|
Identificateur de l’enregistrement | 4c78bc64-0773-48d1-aa1b-df171459ad85 |
---|
Enregistrement créé | 2012-03-09 |
---|
Enregistrement modifié | 2020-04-17 |
---|